Permit No. BLDG2206-0195 Permit Type   COMMERCIAL BUILD-OUT Site Address   10001 OLD CLUB RD
PARKLAND, FL 330763906
Applied   06/16/2022 Applicant   MARY BANMILLER
Approved   06/14/2023 Owner   PARKLAND GOLF & COUNTRY CLUB
Issued   07/20/2023 Contractor   ORIGIN CONSTRUCTION LLC
Parent Permit No.   Description   PGCC SPORTS CLUB RENOVATION
  Notes  
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

 07/20/2023NOCDebbie GrosseAPPROVED

 08/28/2023GROUND ROUGHJeremy HassenplugPARTIAL APPROVAL8/25/2023 2:16:32 PM FM 8/28/2023 1:05:14 PM Partial for front area or reception area pending plans matching.

 08/29/2023DEMO STRUCTURALJoseph RobinsonAPPROVED8/28/2023 10:03:12 AM wth

 09/11/2023GROUND ROUGHJan TranaDISAPPROVED9/8/2023 3:03:52 PM wth 9/11/2023 12:56:03 PM Not ready 9/11/2023 1:16:56 PM Not ready

 09/12/2023GROUND ROUGHJan TranaDISAPPROVED9/11/2023 2:32:48 PM ST 9/12/2023 2:19:44 PM Not per plan Vent below centerline of drain line Incorrect sleeve material.

 09/13/2023STRUCT MISC REPAIRTony WillsonPARTIAL APPROVALPlumbing Trench Repairs9/13/2023 5:23:21 PM First section of plumbing trenches. Contractor hasn't submitted the compaction or termite treatment certificates yet. See the Approved Plans for the areas inspected.

 09/20/2023GROUND ROUGHJan TranaAPPROVED9/19/2023 2:57:38 PM wth

 09/21/2023SEWER CONNECTIONJan TranaAPPROVED9/20/2023 10:21:27 AM MT

 10/06/2023FRAMINGWyatt T. HaygoodPARTIAL APPROVAL10/5/2023 9:04:50 AM VB 10/6/2023 12:31:44 PM Walls above hard ceiling areas approved. Hi hat framing and ceiling insulation on bottom of truss cords approved

 10/06/2023SOIL TERMITE TREATWyatt T. HaygoodAPPROVED10/6/2023 12:58:19 PM soil termite treatment for trenches submitted and approved

 10/17/2023UNDERGROUNDJoe NievesAPPROVED10/16/2023 7:51:23 AM VB 10/17/2023 1:10:04 PM GYM AREA FLOOR BOXES / BOXES CONTAIN DATA/POWER. AREA FRONT OF OFFICE.

 10/19/2023FRAMINGTony WillsonPARTIAL APPROVAL10/17/2023 3:51:24 PM JS 10/19/2023 7:25:05 AM Fitness Area Soffits. See highlighted plans.

 10/23/2023SLABJoseph RobinsonAPPROVED

 11/02/2023SECOND ROUGHJan TranaPARTIAL APPROVAL10/31/2023 1:34:00 PM FM

 11/08/2023ELEC WALL ROUGHJoe NievesAPPROVED11/7/2023 4:31:24 PM JS 11/8/2023 2:11:59 PM SEE PERMIT WITH ROOM NUMBERS/ AREAS APPROVED

 11/08/2023ELECTRIC ROUGHJoe NievesAPPROVED11/8/2023 2:12:03 PM SEE PERMIT WITH ROOM NUMBERS/AREAS APPROVED

 11/15/2023ROUGH DUCTDave Chin-SangPARTIAL APPROVAL11/14/2023 2:08:57 PM VB 11/15/2023 11:34:27 AM COP for ductwork with sizes and location Show relocation of balancing dampers from main trunk lines Confirm Return duct and grill size for AHU-3 on MF101 B Relocation of EXF 7

 11/21/2023TIE BEAM/BONDTony WillsonDISAPPROVEDTB @ Kids Area SHT - SS102B11/21/2023 3:40:05 PM Deficiencies Found: 1) All TB steel (Rebar) needs to be continuous throughout. 2) All drop bars (Filled Cells) need to be hooked into the TB. 3) Plan is showing #5 rebar in all Filled Cells. Appears to be #4 rebar installed. 4) Plan also shows Horizontal Reinforcement installed in masonry. Need to check every other course. Non observed at site. (FBC110.9.1)

 11/28/2023SECOND ROUGHJan TranaPARTIAL APPROVALJOSE 786238062711/28/2023 10:16:50 AM Hot water partition insulation

 11/28/2023FRAMINGTony WillsonPARTIAL APPROVALLOCKER ROOM11/28/2023 3:51:48 PM Work west of the Locker Rooms (walls only) are approved. See Plan Highlighted>

 11/30/2023SECOND ROUGHJan TranaPARTIAL APPROVALIF NEEDED CALL 786-238-062711/29/2023 12:17:01 PM FM 11/30/2023 12:05:38 PM Sanitary, water supply, insulation in gang bathrooms.

 11/30/2023TIE BEAM/BONDJoseph RobinsonDISAPPROVED11/29/2023 11:01:18 AM ST 11/30/2023 4:31:02 PM Same as previous disapproval.

 11/30/2023INSULATIONAnthony CrisantiPARTIAL APPROVALTREAMENT ROOMS11/29/2023 10:53:29 AM MT 11/30/2023 4:35:26 PM Insulation completed in all therapy rooms

 12/01/2023DRYWALL SCREWAnthony CrisantiPARTIAL APPROVAL11/30/2023 3:29:16 PM FM 12/1/2023 7:51:44 AM pm 12/1/2023 2:50:24 PM Notes on plans for partial

 12/11/2023TIE BEAM/BONDJoseph RobinsonDISAPPROVED12/8/2023 4:47:36 PM FM 12/11/2023 12:56:37 PM No special inspector report. Special inspector must address all items that don't match the plans. Items #4 steel up bars, corner bars and in tie beam instead of #5. Horizontal reinforcement cut in several areas.

 12/19/2023TIE BEAM/BONDJoseph RobinsonDISAPPROVED12/19/2023 3:40:00 PM No certification letter. No contractor representative. Time of inspection 3:40pm

 12/20/2023TIE BEAM/BONDJoseph RobinsonAPPROVED

 12/27/2023SECOND ROUGHJan TranaAPPROVEDSTEAM SHOWERS12/22/2023 8:28:17 AM MT

 12/28/2023FRAMINGTony WillsonPARTIAL APPROVAL12/27/2023 11:58:02 AM JS 12/28/2023 7:20:45 AM Inspector BD40 changed the inspection assignment from BD40 to BD35 12/28/2023 2:37:58 PM Walls approved not ceilings. The kids room is the last to be inspected for framing. Not Ready

 01/03/2024PRESSURE TEST-FIRELici MerrittAPPROVED1/2/2024 1:05:42 PM vb

 01/03/2024ROUGH FIRE SPRINKLERLici MerrittPARTIAL APPROVAL1/2/2024 1:05:51 PM vb 1/3/2024 3:04:32 PM See plans for the areas that have been visually checked. Captain Lici Merritt Amerritt@coralsprings.gov

 01/09/2024ROUGH DUCTDave Chin-SangCANCELLED BY PERMITE1/8/2024 1:38:35 PM Request For Inspection City of Parkland Request for Inspection Form Permit Number 22060195 First Name Jose Last Name Padron Company Arras Air Phone Number 786-800-7369 Email Address permits@arrasair.us Type of Inspection(s) Requested Partial duct rough Request Date 1/9/2024 Instructions/Example If you desire an inspection on the 28th, your request must be submitted by 4:00PM on the 27th. Additional Information Contractors can schedule inspections online by going to https://www.cityofparkland.org/epermit. If you are a contractor and do not have access to eTRAKiT please contact the Building Department to get directions for scheduling inspections online. Contractors can cancel inspections online up to 6:00am via the online portal. Same day inspection cancellations you must contact the Building Department via telephone between 7:30 and 8:00 AM at 954.753.5447. Request For Inspection City of Parkland Request for Inspection Form Permit Number 22060195 First Name Jose Last Name Padron Company Arras Air Phone Number 786-800-7369 Email Address permits@arrasair.us Type of Inspection(s) Requested Partial duct rough Request Date 1/9/2024 Instructions/Example If you desire an inspection on the 28th, your request must be submitted by 4:00PM on the 27th. Additional Information Contractors can schedule inspections online by going to https://www.cityofparkland.org/epermit. If you are a contractor and do not have access to eTRAKiT please contact the Building Department to get directions for scheduling inspections online. Contractors can cancel inspections online up to 6:00am via the online portal. Same day inspection cancellations you must contact the Building Department via telephone between 7:30 and 8:00 AM at 954.753.5447.

 01/12/2024ELEC CEILING ROUGHJoe NievesPARTIAL APPROVAL1/11/2024 10:05:51 AM ST 1/12/2024 2:49:16 PM ELECTRIC CEILING ROUGH/FOLLOWING AREAS: GYM RECEPTION KID DAYCARE RESTROOMS

 01/16/2024ROUGH DUCTDave Chin-SangPARTIAL APPROVAL1/16/2024 10:40:01 AM Functional fitness, Cop reception exhaust main EXF 7 Not inspected. Storage room 195 not done.

 01/16/2024ELEC CEILING ROUGHJoe NievesAPPROVED1/12/2024 3:20:19 PM MT

 01/24/2024VENTILATION ROUGHDave Chin-SangAPPROVED1/23/2024 10:08:49 AM ST

 01/24/2024EXHAUST ROUGHDave Chin-SangAPPROVED1/23/2024 10:09:44 AM ST

 01/24/2024ROUGH DUCTDave Chin-SangAPPROVED1/23/2024 10:08:16 AM ST

 01/24/2024WIND/DOOR BUCKAnthony CrisantiAPPROVED1/24/2024 7:47:19 AM 10-12

 01/24/2024WIND/DOOR ATTACHMENTAnthony CrisantiDISAPPROVED1/24/2024 7:46:55 AM 10-12 1/24/2024 1:09:08 PM Not ready

 01/24/2024FIRE ALARM ROUGH ELJoe NievesPARTIAL APPROVAL1/23/2024 2:02:27 PM ST 1/24/2024 3:03:42 PM [ABANDONED LOW VOLTAGE CABLES ABOVE CEILING MUST BE REMOVED] THIS IS IN COMPLIANCE WITH THE FOLLOWING [NATIONAL ELECTRIC CODE] ARTICLES: NEC 820.25 NEC 800.25 NEC 770.25 NEC 760.25 NEC 725.25

 01/26/2024FRAMINGAnthony CrisantiAPPROVED1/25/2024 11:41:30 AM FM 1/26/2024 7:46:08 AM 12-4 1/26/2024 4:02:06 PM All framing now buttoned up walls and ceilings Will check on drop ceilings Monday 1/29/24

 01/29/2024PRESSURE TEST-FIREBruno MatosPARTIAL APPROVAL1/29/2024 12:12:15 PM Partial rough and pressure

 01/29/2024ROUGH FIRE SPRINKLERBruno MatosPARTIAL APPROVAL1/29/2024 12:14:41 PM Partial rough and pressure. Tennis pro not done Kids area not done Other locations not done because of ceiling. Noted on plans what was done.

 01/30/2024LOW VOLTAGE ROUGHRinor KrasniqiPARTIAL APPROVALWIFI,CAM,SPKS1/30/2024 11:17:53 AM LV rough Cables shall be supported and off the grid 800.110 Please move cable from recessed light 110.3 Fire foam/calk fire rated penetrations FBC 714.4

 01/30/2024WIND/DOOR ATTACHMENTAnthony CrisantiPARTIAL APPROVAL1/29/2024 1:48:18 PM ST 1/30/2024 1:18:40 PM 3 windows and 1 double door was inspected and approved. 2 doors yet to be installed and finished. Will call once those are installed.

 01/31/2024LOW VOLTAGE ROUGHRinor KrasniqiDISAPPROVED1/30/2024 3:38:15 PM vb 1/31/2024 1:41:28 PM Awaiting photos of straps

 01/31/2024FIRE ALARM ROUGH ELRinor KrasniqiAPPROVED1/30/2024 3:36:28 PM vb

 02/01/2024LOW VOLTAGE ROUGHRinor KrasniqiPARTIAL APPROVAL2/1/2024 12:53:33 PM All but group exercise pass LV rough

 02/02/2024ROUGH FIRE SPRINKLERLici MerrittPARTIAL APPROVAL1/31/2024 2:49:03 PM JS 2/2/2024 6:45:44 AM See plans for areas approved. Captain Lici Merritt

 02/08/2024SHOWER PANJan TranaDISAPPROVED2/7/2024 1:39:07 PM FM 2/8/2024 11:59:54 AM 2020 FPC 312.9 Pipe from drain not plugged.

 02/12/2024SHOWER PANScott WieselAPPROVED2/8/2024 12:31:30 PM FM

 02/16/2024DRYWALL SCREWAnthony CrisantiAPPROVED2/15/2024 3:51:59 PM FM 2/16/2024 9:05:18 AM All finished walls, ceilings and wet areas (den shield)

 04/16/2024WIND/DOOR ATTACHMENTJoseph RobinsonAPPROVED

 04/16/2024INSULATIONJoseph RobinsonAPPROVED

 04/16/2024WATER TAPPerry TabornAPPROVED4/15/2024 11:52:30 AM ST

 04/16/2024TOP OUTJan TranaAPPROVED4/15/2024 11:52:57 AM ST

 04/17/2024LOW VOLTAGE ROUGHRinor KrasniqiDISAPPROVED4/16/2024 4:46:19 PM FM 4/17/2024 9:15:32 AM 110.9 no access everything closed up

 04/17/2024ROUGH FIRE SPRINKLERBruno MatosAPPROVED4/16/2024 4:44:22 PM ST

 04/17/2024STRUCT MISC REPAIRTony WillsonAPPROVED4/16/2024 4:46:06 PM FM 4/17/2024 12:44:05 PM Plumbing Trenches.

 04/18/2024LOW VOLTAGE ROUGHRinor KrasniqiAPPROVED4/17/2024 11:16:21 AM FM

 04/19/2024SMOKE DETECTOR TESTDave Chin-SangAPPROVED4/18/2024 3:29:50 PM FM 4/19/2024 9:54:58 AM RTU 1&3 with Bruno from Fire no permit paperwork to sign

 04/19/2024FIRE ALARM FIREBruno MatosDISAPPROVED4/18/2024 2:39:20 PM MT 4/19/2024 2:11:26 PM Need to test tampers and flow. Provide music shutdown relay Horns and voice evac does not meet (db) levels required by NFPA 72 Tested all initiating devices and duct detectors. Need to test and check all horn strobes.

 04/22/2024SEWER FINALJan TranaAPPROVED4/18/2024 1:40:17 PM MT

 04/22/2024PLUMBING FINALJan TranaPARTIAL APPROVAL4/22/2024 11:04:24 AM Lavatory faucets are loose, chrome outer sleeve moves, check manufacturer installation's instructions

 04/23/2024PLUMBING FINALJan TranaCANCELLED BY PERMITE4/22/2024 3:53:54 PM vb

 04/23/2024FINAL FIRE SPRINKBruno MatosDISAPPROVED - FEE4/22/2024 3:09:38 PM VB 4/23/2024 10:38:40 AM ** WORK NOT READY. ** SPRINKLERS HEADS WERE REMOVED AND BEING REPLACED ** ESCUTCHEON PLATES MISSING

 04/23/2024LOW VOLTAGE FINALRinor KrasniqiDISAPPROVEDWIFI,CAM,SPKS4/23/2024 11:14:34 AM 107.3 not to plan missing speakers 107.3 missing camera Outdoor playground Front desk

 04/24/2024FINAL FIRE SPRINKBruno MatosPARTIAL APPROVAL4/23/2024 3:16:24 PM MT 4/24/2024 10:33:20 AM Provide spare blue bulb in sprinkler repair kit PIV and OS&Y needs to be locked/secured. Repairs required for existing fire sprinkler system. Red tagged - provide paperwork.

 04/24/2024FIRE ALARM FINAL ELJoe NievesDISAPPROVED4/23/2024 3:30:05 PM FM 4/24/2024 11:33:55 AM [FIRE DEPARTMENT/ FIRE ALARM FINAL] INSPECTION MUST BE SCHEDULED [BEFORE ELECTRIC FIRE ALARM FINAL] OR IN CONJUNCTION. FBC-BCA 107.1 [INSPECTIONS]

 04/24/2024PLUMBING FINALJan TranaPARTIAL APPROVAL4/23/2024 2:39:20 PM PLMBG CONT 4/24/2024 12:48:27 PM Pending faucet notarized letter from owner/architect/contractor assuming all responsibility for the faucet installation issues.

 04/24/2024MECHANICAL FINALDave Chin-SangPARTIAL APPROVAL4/23/2024 1:06:55 PM FM 4/24/2024 12:49:13 PM RTU model cop Area served label rooftop equipment Mounting details for c/u

 04/25/2024LOW VOLTAGE FINALRinor KrasniqiDISAPPROVED4/24/2024 1:17:21 PM FM 4/25/2024 9:53:22 AM Awaiting as built 703.2.3 approved fire blocking in IT closet

 04/26/2024MECHANICAL FINALDave Chin-SangPARTIAL APPROVAL4/25/2024 3:37:07 PM FM 4/26/2024 10:52:07 AM Pending Engineering letter for Equipment model numbers

 04/26/2024ELECTRIC FINALJoe NievesDISAPPROVED4/25/2024 3:33:45 PM FM 4/26/2024 12:59:28 PM GYM FLOOR BOXES WIRED [INCORRECTLY] NEC 110.3 B

 04/29/2024LOW VOLTAGE FINALJoe NievesDISAPPROVED4/26/2024 2:36:59 PM FM 4/29/2024 11:55:55 AM THE LOW VOLTAGE WIRING INSTALLED WITHIN THE [GYM FLOOR FLOOR BOXES] HAVE NOT BEEN INSTALLED ACCORDING TO THE MANUFACTURERS INSTRUCTIONS/SPECIFICATIONS. NEC 110.3 B

 04/30/2024PLUMBING FINALCGA PLUMBINGPARTIAL APPROVAL4/30/2024 12:43:01 PM APPROVED PENDING BACKFLOW CERTIFICATES 4/30/2024 4:10:49 PM STILL PENDING LETTER CONCERNING FAUCETS

 04/30/2024ZONING INSPECTIONJean PanebiancoAPPROVEDn4/25/2024 11:58:11 AM MT 4/30/2024 4:15:04 PM N/a

 05/02/2024LOW VOLTAGE FINALRinor KrasniqiAPPROVED5/1/2024 9:48:15 AM MT

 05/02/2024ELECTRIC FINALRinor KrasniqiDISAPPROVED5/1/2024 9:47:57 AM MT 5/2/2024 12:56:17 PM 760.41 Fire breaker lock red 406.12 child care tamper receptacles 110.12 close unused openings on panels and luminaries 300.4 plastic fiber bushing awg 4 and larger FBC BCA 110.5 incomplete Emergency lights non operable/missing indicator Missing face plate on receptacle Hole larger than 1/16 on Sheetrock above receptacle Fire block missing in panel room and it room

 05/03/2024MECHANICAL FINALDave Chin-SangAPPROVED5/3/2024 6:50:49 AM Engineer letter for equipment and T&B report received and sent to scanning

 05/03/2024FIRE ALARM FIREBruno MatosAPPROVED

 05/03/2024FINAL FIRE SPRINKBruno MatosAPPROVED5/2/2024 11:53:26 AM mt

 05/03/2024PLUMBING FINALJan TranaAPPROVED5/2/2024 9:30:22 AM MT

 05/03/2024FIRE ALARM FINAL ELJoe NievesAPPROVED

 05/06/2024ELECTRIC FINALRinor KrasniqiAPPROVED5/3/2024 12:47:18 PM FM

 05/07/2024BTR ON FILEJuan SotoAPPROVEDREACTIVATED BTR LICENSE 312

 05/07/2024FINAL INSPECT-FIREThomas HayesAPPROVED5/7/2024 12:32:06 PM Only%20portions%20that%20were%20renovated;%20not%20entire%20structure.

 05/08/2024ADA COMPLIANCEJoseph RobinsonAPPROVEDSCHEDULE WITH FINAL5/7/2024 12:14:02 PM JS - SIGNED PERMIT CARD EMAILED, CONFIRMING FINAL FIRE INSPECTION WAS PASSED 5/7/2024

 05/08/2024FINALJoseph RobinsonAPPROVED5/7/2024 12:14:25 PM JS - SIGNED PERMIT CARD EMAILED, CONFIRMING FINAL FIRE INSPECTION WAS PASSED 5/7/2024 5/8/2024 3:03:59 PM ROOM OCCUPANT LOADS NOT POSTED - OWNER ORDERED CUSTOM SIGNS. TOLD TO PLACE TEMPORARY SIGNS UP TO COMPLIY FIRE CODE

 05/31/2024ADMIN CHECKLIST**Victoria BarriosAPPROVED