10/17/2023 | NOC | Stephanie Taylor | APPROVED | | |
|
11/14/2023 | UNDERGROUND | Pedro Vieira | DISAPPROVED | eTRAKiT Inspection Request | 11/13/2023 8:22:31 AM
11/13/2023 8:22 AM RELIABLE POWER SYSTEMS
Contact Name: RELIABLE POWER SYSTEMS
Site Address: 7773 MARVANNA LN
Phone: 5613624484
e-Mail: PC@justcallreliable.com
11/14/2023 8:47:30 AM
Not ready/complete
|
|
11/14/2023 | ELECTRIC ROUGH | Pedro Vieira | DISAPPROVED | eTRAKiT Inspection Request | 11/13/2023 8:22:39 AM
11/13/2023 8:22 AM RELIABLE POWER SYSTEMS
Contact Name: RELIABLE POWER SYSTEMS
Site Address: 7773 MARVANNA LN
Phone: 5613624484
e-Mail: PC@justcallreliable.com
11/14/2023 8:47:31 AM
Not ready/complete
|
|
11/14/2023 | GAS LINE RGH OUT-PL | Jan Trana | APPROVED | eTRAKiT Inspection Request | 11/13/2023 8:30:31 AM
11/13/2023 8:30 AM RELIABLE POWER SYSTEMS
Contact Name: RELIABLE POWER SYSTEMS
Site Address: 7773 MARVANNA LN
Phone: 5613624484
e-Mail: PC@justcallreliable.com
|
|
11/29/2023 | UNDERGROUND | Rinor Krasniqi | DISAPPROVED - FEE | eTRAKiT Inspection Request | 11/28/2023 9:12:08 AM
11/28/2023 9:12 AM RELIABLE POWER SYSTEMS
Contact Name: RELIABLE POWER SYSTEMS
Site Address: 7773 MARVANNA LN
Phone: 5613624484
e-Mail: PC@justcallreliable.com
11/29/2023 11:22:17 AM
12" is not sufficient as per T300.5
|
|
11/29/2023 | ELECTRIC ROUGH | Rinor Krasniqi | DISAPPROVED - FEE | eTRAKiT Inspection Request | 11/28/2023 9:12:16 AM
11/28/2023 9:12 AM RELIABLE POWER SYSTEMS
Contact Name: RELIABLE POWER SYSTEMS
Site Address: 7773 MARVANNA LN
Phone: 5613624484
e-Mail: PC@justcallreliable.com
11/29/2023 11:22:19 AM
250.24 bond grounding electrode system to service supplied AC system
110.14 No insulation under conductor terminals
110.3 SPD under ATS A not solidly mounted
|
|
12/04/2023 | UNDERGROUND | Joe Nieves | APPROVED | eTRAKiT Inspection Request | 11/30/2023 4:54:39 PM
11/30/2023 4:54 PM RELIABLE POWER SYSTEMS
after 11am if possible
Contact Name: RELIABLE POWER SYSTEMS
Site Address: 7773 MARVANNA LN
Phone: 5613624484
e-Mail: PC@justcallreliable.com
11/30/2023 4:57:28 PM
11/30/2023 4:57 PM RELIABLE POWER SYSTEMS
permit hanging from electrical service
Contact Name: RELIABLE POWER SYSTEMS
Site Address: 7773 MARVANNA LN
Phone: 5613624484
e-Mail: PC@justcallreliable.com
|
|
12/04/2023 | ELECTRIC ROUGH | Joe Nieves | DISAPPROVED | eTRAKiT Inspection Request | 11/30/2023 4:57:08 PM
11/30/2023 4:57 PM RELIABLE POWER SYSTEMS
permit hanging from electrical service
Contact Name: RELIABLE POWER SYSTEMS
Site Address: 7773 MARVANNA LN
Phone: 5613624484
e-Mail: PC@justcallreliable.com
12/4/2023 12:38:57 PM
1) A NEUTRAL TO CASE CONNECTION IS NOT PERMITTED WITHIN THE [SECOND LOAD CENTER].
2) BRANCH CIRCUIT IDENTIFICATION [MUST] BE PRINTED LABELS SUITABLE FOR THE ENVIRONMENT.
NEC 250.24 A 5
NEC 110.22
|
|
12/06/2023 | ELECTRIC ROUGH | Pedro Vieira | APPROVED | eTRAKiT Inspection Request | 12/5/2023 3:16:27 PM
12/5/2023 3:16 PM RELIABLE POWER SYSTEMS
Contact Name: RELIABLE POWER SYSTEMS
Site Address: 7773 MARVANNA LN
Phone: 5613624484
e-Mail: PC@justcallreliable.com
|
|
01/02/2024 | MECHANICAL FINAL | Dave Chin-Sang | APPROVED | eTRAKiT Inspection Request | 12/29/2023 9:17:10 AM
12/29/2023 9:17 AM RELIABLE POWER SYSTEMS
Contact Name: RELIABLE POWER SYSTEMS
Site Address: 7773 MARVANNA LN
Phone: 5613624484
e-Mail: PC@justcallreliable.com
|
|
01/02/2024 | FINAL GAS-PLUMBING | Jan Trana | APPROVED | eTRAKiT Inspection Request | 12/29/2023 9:17:19 AM
12/29/2023 9:17 AM RELIABLE POWER SYSTEMS
Contact Name: RELIABLE POWER SYSTEMS
Site Address: 7773 MARVANNA LN
Phone: 5613624484
e-Mail: PC@justcallreliable.com
|
|
01/23/2024 | LANDSCAPING | Patti Hoot | APPROVED | eTRAKiT Inspection Request | 1/22/2024 3:33:54 PM
1/22/2024 3:34 PM RELIABLE POWER SYSTEMS
Contact Name: RELIABLE POWER SYSTEMS
Site Address: 7773 MARVANNA LN
Phone: 5613624484
e-Mail: PC@justcallreliable.com
|
|
02/02/2024 | ELECTRIC FINAL** | Rinor Krasniqi | APPROVED | | |
|