05/03/2024
6:17 AM
 
Permit No. BLDG2103-0144 Permit Type   ADDITION Site Address   10520 NW 67 CT
PARKLAND, FL 330762910
Applied   03/12/2021 Applicant  
Approved   06/23/2021 Owner   IZA,GLADYS
Issued   07/01/2021 Contractor   HIGHER LIVING CONSTRUCTION INC
Parent Permit No.   Description   ADDITION & INT REMODEL
  Notes  
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

 07/01/2021NOCJuan SotoAPPROVED

 07/01/2021PRODUCT APPROVALSWyatt T. HaygoodAPPROVED

 08/02/2021GROUND ROUGHJeremy HassenplugPARTIAL APPROVAL7/30/2021 2:55:29 PM VB 8/2/2021 1:43:16 PM Outside sewer only. Ground rough needs water with 5' head test. Also cop needed by final see pics in iPad

 08/25/2021GROUND ROUGHJan TranaAPPROVED8/24/2021 3:22:54 PM st 8/25/2021 1:01:52 PM COP required by final ISO orientation

 09/30/2021SOIL BEARING CERTBill TracyAPPROVED9/30/2021 11:38:19 AM STATEMENT OF SOIL BEARING FROM NUTTING ENGINEERS, WITH BORING LOG AND COMPACTIONS, ATTESTING TO A BEARING CAPACITY OF 2500 PSF

 10/22/2021SOIL TERMITE TREATWyatt T. HaygoodAPPROVED

 10/25/2021SLABWyatt T. HaygoodDISAPPROVED10/22/2021 10:26:12 AM wth 10/25/2021 11:25:13 AM Transfer steel not installed. Transverse steel not installed. Steel in footing requires three inch minimum concrete coverage.

 10/29/2021SLABAlejandro CorralesAPPROVED10/28/2021 2:55:55 PM VB

 01/21/2022CONSULTATIONWyatt T. HaygoodAPPROVED

 02/11/2022SPOT SURVEYBill TracyAPPROVED

 02/16/2022TRUSS PLANS ON FILEDebbie GrosseAPPROVEDSUBMITTED ONLY

 02/18/2022TIE BEAM/BONDAlejandro CorralesDISAPPROVED2/17/2022 10:11:37 AM vb 2/18/2022 3:25:10 PM Not ready for inspection. Tie beam incomplete in multiple locations. Column steel is sticking out of masonry. Some down bars missing. Finish 100% and reschedule

 03/25/2022TIE BEAM/BONDAlejandro CorralesDISAPPROVED3/24/2022 9:24:49 AM VB 3/25/2022 4:50:44 PM Contractor was supposed to send me a photo of the corrected tie-beam at the double 45 degree corner. By 5pm on Friday, I have not received requested photos. reschedule for Monday.

 03/30/2022TIE BEAM/BONDAlejandro CorralesAPPROVED

 04/11/2022TRUSSJoseph RobinsonCANCELLED BY PERMITETRUSS ENGINEERING SUBMITTED4/8/2022 4:13:40 PM JS

 04/11/2022ROOF SHEATHINGJoseph RobinsonCANCELLED BY PERMITE4/8/2022 4:13:29 PM JS

 04/12/2022ROOF SHEATHINGAlejandro CorralesAPPROVED4/11/2022 2:57:50 PM ST

 04/12/2022TRUSSAlejandro CorralesDISAPPROVED4/11/2022 2:58:10 PM ST 4/12/2022 3:50:00 PM 1) There are a couple of trusses above addition entry where the embedded strap does not wrap around truss or have at least 1 back nail. 2) there are 9 consecutive missed embedded straps. Surface mounted twist straps were used in their place. Verify if engineer requires a missed strap affidavit for this area. Provide detail in plan or letter from engineer verifying these twist straps can be used in lieu of embedded straps.

 04/13/2022TIN CAPJoseph RobinsonDISAPPROVED4/12/2022 4:44:53 PM ST 4/13/2022 2:12:05 PM Work in progress. Not ready for inspection.

 04/13/2022HOT MOP IN PROGRESSJoseph RobinsonDISAPPROVED4/12/2022 4:45:42 PM ST 4/13/2022 2:13:17 PM Schedule this inspection after passing tin cap inspection. Peel and stick must be 100% at time of inspection.

 04/14/2022HOT MOP IN PROGRESSAlejandro CorralesAPPROVED4/13/2022 3:58:41 PM ST

 04/14/2022TIN CAPAlejandro CorralesAPPROVED4/13/2022 3:58:12 PM ST

 04/22/2022TRUSSWill JorgeCANCELLED BY PERMITE4/21/2022 3:24:22 PM MT

 04/22/2022WIND/DOOR BUCKWill JorgeCANCELLED BY PERMITE4/21/2022 3:24:36 PM MT

 05/24/2022WIND/DOOR BUCKAlejandro CorralesAPPROVED

 05/24/2022TRUSSAlejandro CorralesAPPROVED5/23/2022 3:53:53 PM ST

 05/26/2022ELECTRIC ROUGHDean DiBisceglieAPPROVED

 06/10/2022UNIT MASONRY CERTWyatt T. HaygoodAPPROVED

 06/13/2022WIRE LATHWyatt T. HaygoodAPPROVEDfor Wyatt6/10/2022 2:43:37 PM wth

 06/13/2022WALL SHEATHINGWyatt T. HaygoodAPPROVEDfor Wyatt6/10/2022 2:44:05 PM wth

 06/13/2022LOW VOLTAGE ROUGHJoe NievesAPPROVEDTV & WIFI6/10/2022 2:41:28 PM wth

 06/24/2022EXHAUST ROUGHDave Chin-SangAPPROVED6/23/2022 10:43:18 AM JS

 06/24/2022ROUGH DUCTDave Chin-SangDISAPPROVED6/23/2022 10:43:59 AM JS 6/24/2022 11:26:45 AM All ductwork sizes not to approved plan . Plastic inner cores of flex duct needs to be sealed (UL 181 Tape Or mastic) M160.4 All ductwork must be elevated to allow for ceiling insulation Condensate line not per plan A/H Closet not large enough . M1305.1

 07/05/2022ROUGH DUCTDave Chin-SangAPPROVEDCOP for Duct,Equip,Size7/1/2022 4:22:02 PM JS

 07/11/2022TOP OUTJan TranaDISAPPROVED7/7/2022 3:12:25 PM ST 7/11/2022 11:47:23 AM Not ready

 07/14/2022TOP OUTJan TranaDISAPPROVED7/13/2022 3:55:28 PM AN 7/14/2022 1:04:28 PM Not ready 7/14/2022 1:04:53 PM Not ready

 07/06/2022FRAMINGAlejandro CorralesAPPROVED7/5/2022 3:06:41 PM VB

 07/11/2022INSULATIONWyatt T. HaygoodDISAPPROVED7/7/2022 3:12:52 PM ST 7/11/2022 12:34:03 PM Trusses are not designed for storage, remove plywood on bottom cords. Baffles required to be installed at soffit vent locations. Attic access required to be 22 inch x 30 inch minimum size.

 07/14/2022INSULATIONAlejandro CorralesCANCELLED BY PERMITE7/13/2022 3:54:59 PM AN

 07/15/2022TOP OUTJan TranaAPPROVED7/14/2022 3:53:27 PM MT 7/15/2022 12:20:21 PM COP required by final Outside sink added Inside sink relocated Sewer orientation 7/15/2022 12:25:35 PM COP required by final Outside sink added Inside sink relocated Sewer orientation

 07/15/2022INSULATIONWyatt T. HaygoodCANCELLED BY PERMITE7/14/2022 3:52:39 PM MT 7/15/2022 7:42:05 AM JS - PER MIKE

 07/18/2022INSULATIONWyatt T. HaygoodCANCELLED BY PERMITE7/18/2022 8:06:56 AM wth

 07/19/2022INSULATIONAlejandro CorralesAPPROVED7/18/2022 3:53:19 PM ST

 07/26/2022DRYWALL SCREWJoseph RobinsonDISAPPROVED7/25/2022 3:23:29 PM VB 7/26/2022 3:15:41 PM Ceilings, walls, and bathroom area missing screws. Work incomplete.

 07/27/2022DRYWALL SCREWJoseph RobinsonAPPROVED7/26/2022 3:23:52 PM JS

 08/05/2022TILE IN PROGRESSAlejandro CorralesAPPROVEDNEEDS UPDATED INSURANCE8/4/2022 9:41:54 AM an

 08/24/2022ROOF TILE UPLIFT TSTBill TracyAPPROVED8/24/2022 4:52:22 PM UPLIFT REPORT SUBMITTED FROM FEDERAL ENGINEERING - PASS

 09/20/2022ROOF FINALAlejandro CorralesAPPROVED

 10/07/2022MECHANICAL FINALDave Chin-SangDISAPPROVED10/6/2022 4:00:42 PM MT 10/7/2022 10:47:19 AM Locking caps required Insulation outside needs UL protection Condensate drain double trapped Low voltage wires @C/U needs protection

 10/10/2022ELECTRIC FINALJoe NievesDISAPPROVED10/6/2022 4:01:29 PM MT 10/7/2022 12:15:00 PM (CHANGE OF PLAN REQUIRED) Approved Electrical Plan Shall Match The Actual Field Installation. Approved Plan Not On Site/ FBC 107.3.1

 10/10/2022PLUMBING FINALJeremy HassenplugAPPROVED

 12/01/2022MECHANICAL FINALScott WieselAPPROVED11/30/2022 11:12:27 AM vb

 12/08/2022ELECTRIC FINALRinor KrasniqiDISAPPROVED12/7/2022 10:59:54 AM CJ 12/8/2022 11:20:49 AM 410.5 no live parts in luminaries; attic 110.8 gfci readily accessible; eve by back door gfci 15' up

 12/08/2022LOW VOLTAGE FINALRinor KrasniqiAPPROVEDTV & WIFI12/7/2022 12:44:02 PM CJ

 12/08/2022CONDENSATE LINEJeremy HassenplugAPPROVED12/7/2022 10:58:30 AM CJ

 12/08/2022FINAL SURVEYWyatt T. HaygoodDISAPPROVED12/8/2022 12:10:52 PM (1). Elevation Certificate required to be submitted. (2). Final Survey is required to be submitted after all elements of construction are complete. Please note that spot survey dated 1-26-2022 was submitted.

 12/08/2022WIND/DOOR ATTACHMENTJoseph RobinsonAPPROVED12/7/2022 12:43:00 PM CJ

 12/12/2022ELECTRIC FINALRinor KrasniqiAPPROVED

 12/09/2022ELECTRIC FINALRinor KrasniqiDISAPPROVEDGFI OCPD REQUIRED. REC TOO HIGH AT EVE.12/8/2022 2:23:51 PM JS 12/9/2022 11:43:00 AM Pending weather resistant receptacle in the eve

 12/23/2022FINAL SURVEYBill TracyAPPROVED12/23/2022 1:12:45 PM 13.43 NAVD X ZONE

 12/28/2022ZONING INSPECTIONJean PanebiancoAPPROVED12/27/2022 8:20:48 AM MT

 12/29/2022FINALAlejandro CorralesAPPROVED12/28/2022 3:56:57 PM CJ

 12/30/2022ADMIN CHECKLIST**Victoria BarriosAPPROVED12/14/2022 3:07:01 PM FINAL TERMITE TREATMENT SUBMITTED SPEC SHEET FOR BLOWN INSULATION SUBMITTED 12/21/2022 1:09:46 PM SPEC SHEET FOR MANVILLE INSULATION RE-SUBMITTED