05/03/2024
4:11 PM
 
Permit No. ELEC2103-0245 Permit Type   GENERATOR Site Address   10351 LAKE VISTA CT
PARKLAND, FL 33076
Applied   03/18/2021 Applicant  
Approved   04/08/2021 Owner   SERBIN,BRUCE
Issued   04/12/2021 Contractor   RELIABLE POWER SYSTEMS
Parent Permit No.   Description   GENERATOR ON PREFAB SLAB
  Notes  
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

 04/27/2021NOCStephanie TaylorAPPROVED

 04/29/2021GAS LINE RGH OUT-PLJan TranaPARTIAL APPROVALeTRAKiT Inspection Request4/28/2021 11:45:01 AM 4/28/2021 11:45 AM RELIABLE POWER SYSTEMS Contact Name: RELIABLE POWER SYSTEMS Site Address: 10351 LAKE VISTA CT Phone: 5613624484 e-Mail: PC@SUNELECTRICWORKS.COM 4/29/2021 11:15:25 AM 3/4 PE pipe around side door

 04/29/2021UNDERGROUNDJoe NievesDISAPPROVEDeTRAKiT Inspection Request4/28/2021 11:44:52 AM 4/28/2021 11:44 AM RELIABLE POWER SYSTEMS Contact Name: RELIABLE POWER SYSTEMS Site Address: 10351 LAKE VISTA CT Phone: 5613624484 e-Mail: PC@SUNELECTRICWORKS.COM 4/30/2021 7:10:18 AM Generator Exhaust Is Less Than 10ft To The Neighbors Window. Broward County BORA Formal Interpretation # 26 Requires A CO Alarm Installed In The Neighbors House As Close As Possible To (Window) Opening.

 04/30/2021ELECTRIC ROUGHJoe NievesDISAPPROVED4/30/2021 7:15:33 AM Generator Exhaust Is Less Than 10ft To The Neighbors Window. Broward County BORA Formal Interpretation # 26 Requires A CO Alarm Installed In The Neighbors House As Close As Possible To (Window) Opening.

 04/30/2021ELECTRIC ROUGHJoe NievesDISAPPROVEDeTRAKiT Inspection Request4/28/2021 11:45:09 AM 4/28/2021 11:45 AM RELIABLE POWER SYSTEMS Contact Name: RELIABLE POWER SYSTEMS Site Address: 10351 LAKE VISTA CT Phone: 5613624484 e-Mail: PC@SUNELECTRICWORKS.COM 4/30/2021 7:13:05 AM Generator Exhaust Is Less Than 10ft To The Neighbors Window. Broward County BORA Formal Interpretation # 26 Requires A CO Alarm Installed In The Neighbors House As Close As Possible To (Window) Opening.

 05/07/2021GAS LINE RGH OUT-PLDave Chin-SangDISAPPROVEDeTRAKiT Inspection Request5/6/2021 11:14:16 AM 5/6/2021 11:14 AM RELIABLE POWER SYSTEMS Contact Name: RELIABLE POWER SYSTEMS Site Address: 10351 LAKE VISTA CT Phone: 5613624484 e-Mail: pa2@justcallreliable.com 5/7/2021 3:48:24 PM Not ready

 05/10/2021ELECTRIC ROUGHJoe NievesAPPROVEDeTRAKiT Inspection Request5/7/2021 1:46:50 PM 5/7/2021 1:46 PM RELIABLE POWER SYSTEMS Contact Name: RELIABLE POWER SYSTEMS Site Address: 10351 LAKE VISTA CT Phone: 5613624484 e-Mail: pa2@justcallreliable.com

 05/10/2021UNDERGROUNDJoe NievesAPPROVEDeTRAKiT Inspection Request5/7/2021 1:47:11 PM 5/7/2021 1:47 PM RELIABLE POWER SYSTEMS Contact Name: RELIABLE POWER SYSTEMS Site Address: 10351 LAKE VISTA CT Phone: 5613624484 e-Mail: pa2@justcallreliable.com

 05/11/2021GAS LINE RGH OUT-PLJan TranaPARTIAL APPROVALeTRAKiT Inspection Request5/10/2021 1:52:51 PM 5/10/2021 1:52 PM RELIABLE POWER SYSTEMS Contact Name: RELIABLE POWER SYSTEMS Site Address: 10351 LAKE VISTA CT Phone: 5613624484 e-Mail: pa2@justcallreliable.com 5/11/2021 11:08:45 AM 3/4" PE from inside fence to house west wall

 05/18/2021GAS LINE RGH OUT-PLDave Chin-SangAPPROVEDeTRAKiT Inspection Request5/17/2021 10:17:09 AM 5/17/2021 10:17 AM RELIABLE POWER SYSTEMS Contact Name: RELIABLE POWER SYSTEMS Site Address: 10351 LAKE VISTA CT Phone: 5613624484 e-Mail: pa2@justcallreliable.com

 05/19/2021MECHANICAL FINALDave Chin-SangAPPROVEDeTRAKiT Inspection Request5/18/2021 3:38:00 PM 5/18/2021 3:38 PM RELIABLE POWER SYSTEMS Contact Name: RELIABLE POWER SYSTEMS Site Address: 10351 LAKE VISTA CT Phone: 5613624484 e-Mail: pa2@justcallreliable.com

 05/19/2021LANDSCAPINGPatti HootAPPROVEDeTRAKiT Inspection Request5/18/2021 3:38:22 PM 5/18/2021 3:38 PM RELIABLE POWER SYSTEMS Contact Name: RELIABLE POWER SYSTEMS Site Address: 10351 LAKE VISTA CT Phone: 5613624484 e-Mail: pa2@justcallreliable.com 5/19/2021 1:54:02 PM Screened with Clusia

 05/19/2021FINAL GAS-PLUMBINGJeremy HassenplugDISAPPROVEDeTRAKiT Inspection Request5/18/2021 3:38:42 PM 5/18/2021 3:38 PM RELIABLE POWER SYSTEMS Contact Name: RELIABLE POWER SYSTEMS Site Address: 10351 LAKE VISTA CT Phone: 5613624484 e-Mail: pa2@justcallreliable.com 5/19/2021 2:16:00 PM Not ready

 05/26/2021FINAL GAS-PLUMBINGDave Chin-SangDISAPPROVEDeTRAKiT Inspection Request5/20/2021 10:58:58 AM 5/20/2021 10:58 AM RELIABLE POWER SYSTEMS Contact Name: RELIABLE POWER SYSTEMS Site Address: 10351 LAKE VISTA CT Phone: 5613624484 e-Mail: pa2@justcallreliable.com 5/25/2021 10:05:22 AM 5/25/2021 10:05 AM RELIABLE POWER SYSTEMS Contact Name: RELIABLE POWER SYSTEMS Site Address: 10351 LAKE VISTA CT Phone: 5613624484 e-Mail: pa2@justcallreliable.com 5/26/2021 12:32:28 PM COP required for final. PVC vent line are required to be UL 651 . In its entirety FBC / Fuel 403.6.3.

 06/03/2021FINAL GAS-PLUMBINGJan TranaDISAPPROVED - FEEeTRAKiT Inspection Request5/28/2021 1:27:27 PM 5/28/2021 1:27 PM RELIABLE POWER SYSTEMS Contact Name: RELIABLE POWER SYSTEMS Site Address: 10351 LAKE VISTA CT Phone: 5613624484 e-Mail: PC@justcallreliable.com 6/3/2021 11:33:24 AM Corrections from May 26 have not been made. 6/3/2021 11:34:25 AM Corrections from May 26 have not been made.

 06/21/2021FINAL GAS-PLUMBINGJeremy HassenplugDISAPPROVEDeTRAKiT Inspection Request6/18/2021 3:46:45 PM 6/18/2021 3:46 PM RELIABLE POWER SYSTEMS Contact Name: RELIABLE POWER SYSTEMS Site Address: 10351 LAKE VISTA CT Phone: 5613624484 e-Mail: PC@justcallreliable.com 6/21/2021 1:32:19 PM Approved cop not on site

 06/30/2021FINAL GAS-PLUMBINGJeremy HassenplugDISAPPROVED - FEEPermit is inside Tube hanging from meter6/29/2021 11:04:26 AM 6/29/2021 11:04 AM RELIABLE POWER SYSTEMS Permit is on Site-Permit is inside Tube hanging from elec meter. Contact Name: RELIABLE POWER SYSTEMS Site Address: 10351 LAKE VISTA CT Phone: 5612953855 e-Mail: PC@justcallreliable.com 6/30/2021 11:39:54 AM Cop not on site

 07/07/2021FINAL GAS-PLUMBINGJan TranaAPPROVEDeTRAKiT Inspection Request7/6/2021 10:30:22 AM 7/6/2021 10:30 AM RELIABLE POWER SYSTEMS Contact Name: RELIABLE POWER SYSTEMS Site Address: 10351 LAKE VISTA CT Phone: 5613624484 e-Mail: PC@justcallreliable.com

 08/30/2021ELECTRIC FINAL**Joe NievesAPPROVED7th EDITION FORMAL INTERP. CO DETECTOR4/1/2021 8:40:22 AM 7th EDITION FORMAL INTERPRETATION. CO DETECTOR INSTALLATION 8/27/2021 1:39:17 PM VB