05/03/2024
1:05 AM
 
Permit No. ELEC2107-0099 Permit Type   GENERATOR Site Address   12335 S PARKLAND BAY TRL
PARKLAND, FL 33076
Applied   07/12/2021 Applicant  
Approved   07/23/2021 Owner   MA,CHRISTOPHER PHAT
Issued   08/05/2021 Contractor   BRYCO ELECTRIC LLC.
Parent Permit No.   Description   GENERATOR W/ NG ON PRE-FAB SLAB
  Notes  
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

 08/05/2021NOCStephanie TaylorAPPROVED

 04/21/2022GAS LINE RGH OUT-PLJeremy HassenplugDISAPPROVEDeTRAKiT Inspection Request12/8/2021 5:11:40 PM NEED CHANGE OF CONTRACTOR PRIOR TO GAS INSPECTION. BLUE FLAME HAS REMOVED THEMSELVES FROM ALL BRYCO PERMITS. 4/21/2022 5:27:24 AM 4/21/2022 5:27 AM BRYCO ELECTRIC LLC. Contact Name: BRYCO ELECTRIC LLC. Site Address: 12335 S PARKLAND BAY TRL Phone: 5617031989 e-Mail: BRYCOELECTRICLLC@GMAIL.COM 4/21/2022 11:21:25 AM PERMIT CARD NOT POSTED APPROVED PLAN NOT ON SITE Low line pressure

 04/21/2022UNDERGROUNDJoe NievesDISAPPROVEDeTRAKiT Inspection Request4/21/2022 5:27:06 AM 4/21/2022 5:27 AM BRYCO ELECTRIC LLC. Contact Name: BRYCO ELECTRIC LLC. Site Address: 12335 S PARKLAND BAY TRL Phone: 5617031989 e-Mail: BRYCOELECTRICLLC@GMAIL.COM 4/21/2022 1:22:46 PM No Plans / Permit / FBC 110.9.1

 04/21/2022ELECTRIC ROUGHJoe NievesDISAPPROVEDeTRAKiT Inspection Request4/21/2022 5:27:56 AM 4/21/2022 5:27 AM BRYCO ELECTRIC LLC. Contact Name: BRYCO ELECTRIC LLC. Site Address: 12335 S PARKLAND BAY TRL Phone: 5617031989 e-Mail: BRYCOELECTRICLLC@GMAIL.COM 4/21/2022 1:22:47 PM No Plans / Permit / FBC 110.9.1

 04/28/2022GAS LINE RGH OUT-PLJeremy HassenplugDISAPPROVEDeTRAKiT Inspection Request4/27/2022 9:20:06 AM 4/27/2022 9:20 AM BRYCO ELECTRIC LLC. Contact Name: BRYCO ELECTRIC LLC. Site Address: 12335 S PARKLAND BAY TRL Phone: 5617031989 e-Mail: BRYCOELECTRICLLC@GMAIL.COM 4/28/2022 11:41:26 AM Low line pressure

 04/28/2022UNDERGROUNDPedro VieiraAPPROVEDeTRAKiT Inspection Request4/27/2022 9:20:15 AM 4/27/2022 9:20 AM BRYCO ELECTRIC LLC. Contact Name: BRYCO ELECTRIC LLC. Site Address: 12335 S PARKLAND BAY TRL Phone: 5617031989 e-Mail: BRYCOELECTRICLLC@GMAIL.COM 4/28/2022 12:04:26 PM N/R

 04/28/2022ELECTRIC ROUGHPedro VieiraDISAPPROVEDeTRAKiT Inspection Request4/27/2022 9:20:22 AM 4/27/2022 9:20 AM BRYCO ELECTRIC LLC. Contact Name: BRYCO ELECTRIC LLC. Site Address: 12335 S PARKLAND BAY TRL Phone: 5617031989 e-Mail: BRYCOELECTRICLLC@GMAIL.COM 4/28/2022 12:04:27 PM Work not complete

 04/29/2022ELECTRIC ROUGHJoe NievesDISAPPROVED - FEEeTRAKiT Inspection Request4/28/2022 12:16:23 PM 4/28/2022 12:16 PM BRYCO ELECTRIC LLC. Contact Name: BRYCO ELECTRIC LLC. Site Address: 12335 S PARKLAND BAY TRL Phone: 5617031989 e-Mail: BRYCOELECTRICLLC@GMAIL.COM 4/29/2022 10:06:53 AM 1) The Nipple Installed Between The Service Equipment And The ATS Has Been Improperly Installed, Which Now Will Allow Water To Enter Into The Cabinet. 2) The Manner In Which The Polaris Taps Were Installed In The Service, Will Not Allow The Cabinet Dead Front To Be Installed As Designed. 3) Polaris Taps Are Missing The Insulators. 4) The LFNC Entering The Generator Requires Support. NEC 312.2 / 110.12 / 110.14 (B) / 356.30

 04/29/2022GAS LINE RGH OUT-PLJan TranaDISAPPROVED - FEEeTRAKiT Inspection Request4/28/2022 12:16:11 PM 4/28/2022 12:16 PM BRYCO ELECTRIC LLC. Contact Name: BRYCO ELECTRIC LLC. Site Address: 12335 S PARKLAND BAY TRL Phone: 5617031989 e-Mail: BRYCOELECTRICLLC@GMAIL.COM 4/29/2022 11:50:50 AM Low line pressure.

 05/24/2022ELECTRIC ROUGHPedro VieiraDISAPPROVED - FEEeTRAKiT Inspection Request5/23/2022 6:30:42 AM 5/23/2022 6:30 AM BRYCO ELECTRIC LLC. Contact Name: BRYCO ELECTRIC LLC. Site Address: 12335 S PARKLAND BAY TRL Phone: 5617031989 e-Mail: BRYCOELECTRICLLC@GMAIL.COM 5/24/2022 12:12:43 PM Nec 110.12 - the manner in which the taps were installed in the service will not allow the dead front to be installed as designed. Note: please see pictures attached

 06/13/2022GAS LINE RGH OUT-PLJeremy HassenplugAPPROVEDeTRAKiT Inspection Request6/6/2022 12:47:23 PM 6/6/2022 12:47 PM BRYCO ELECTRIC LLC. Contact Name: BRYCO ELECTRIC LLC. Site Address: 12335 S PARKLAND BAY TRL Phone: 5617031989 e-Mail: BRYCOELECTRICLLC@GMAIL.COM 6/11/2022 7:47:51 PM 6/11/2022 7:47 PM BRYCO ELECTRIC LLC. Contact Name: BRYCO ELECTRIC LLC. Site Address: 12335 S PARKLAND BAY TRL Phone: 5617031989 e-Mail: BRYCOELECTRICLLC@GMAIL.COM

 06/07/2022ELECTRIC ROUGHCGAELAPPROVEDeTRAKiT Inspection Request6/6/2022 12:47:40 PM 6/6/2022 12:47 PM BRYCO ELECTRIC LLC. Contact Name: BRYCO ELECTRIC LLC. Site Address: 12335 S PARKLAND BAY TRL Phone: 5617031989 e-Mail: BRYCOELECTRICLLC@GMAIL.COM 6/7/2022 3:01:06 PM Observed correct wire size in place and compliance with bc requirements.TP

 06/14/2022MECHANICAL FINALDave Chin-SangAPPROVEDeTRAKiT Inspection Request6/13/2022 1:54:29 PM 6/13/2022 1:54 PM BRYCO ELECTRIC LLC. Contact Name: BRYCO ELECTRIC LLC. Site Address: 12335 S PARKLAND BAY TRL Phone: 5617031989 e-Mail: BRYCOELECTRICLLC@GMAIL.COM

 06/14/2022FINAL GAS-PLUMBINGDave Chin-SangDISAPPROVEDeTRAKiT Inspection Request12/8/2021 5:11:53 PM NEED CHANGE OF CONTRACTOR PRIOR TO GAS INSPECTION. BLUE FLAME HAS REMOVED THEMSELVES FROM ALL BRYCO PERMITS. 6/13/2022 1:54:49 PM 6/13/2022 1:54 PM BRYCO ELECTRIC LLC. Contact Name: BRYCO ELECTRIC LLC. Site Address: 12335 S PARKLAND BAY TRL Phone: 5617031989 e-Mail: BRYCOELECTRICLLC@GMAIL.COM 6/14/2022 8:58:43 AM Not ready

 06/15/2022FINAL GAS-PLUMBINGJeremy HassenplugDISAPPROVED - FEEeTRAKiT Inspection Request6/14/2022 7:31:34 PM 6/14/2022 7:31 PM BRYCO ELECTRIC LLC. Contact Name: BRYCO ELECTRIC LLC. Site Address: 12335 S PARKLAND BAY TRL Phone: 5617031989 e-Mail: BRYCOELECTRICLLC@GMAIL.COM 6/15/2022 10:53:41 AM Not ready 2nd time

 06/15/2022LANDSCAPINGPatti HootAPPROVEDeTRAKiT Inspection Request6/13/2022 1:53:56 PM 6/13/2022 1:53 PM BRYCO ELECTRIC LLC. Contact Name: BRYCO ELECTRIC LLC. Site Address: 12335 S PARKLAND BAY TRL Phone: 5617031989 e-Mail: BRYCOELECTRICLLC@GMAIL.COM

 06/17/2022FINAL GAS-PLUMBINGDave Chin-SangAPPROVEDeTRAKiT Inspection Request6/16/2022 2:14:43 PM 6/16/2022 2:14 PM BRYCO ELECTRIC LLC. Contact Name: BRYCO ELECTRIC LLC. Site Address: 12335 S PARKLAND BAY TRL Phone: 5617031989 e-Mail: BRYCOELECTRICLLC@GMAIL.COM

 06/22/2022ELECTRIC FINAL**Joe NievesPARTIAL APPROVAL6/21/2022 10:08:04 AM MT 6/22/2022 2:55:57 PM Partial Approval Pending Required Signage On Generator And Service. Work Not Complete/ FBC 110.9.1

 08/23/2022ELECTRIC FINAL**Pedro VieiraDISAPPROVED8/19/2022 8:36:32 AM vb 8/23/2022 3:11:20 PM FBC 110.9.1 - no access - contractor not on site to start Generator 8/23/2022 3:14:09 PM FBC 110.9.1 - no access - contractor not on site to start Generator

 08/26/2022ELECTRIC FINAL**Joe NievesDISAPPROVED8/26/2022 1:07:32 PM TECH REQUIRED FOR GENERATOR START-UP AND TEST/ FBC-BCA 107.1 8/26/2022 1:09:02 PM TECH REQUIRED FOR GENERATOR START-UP AND TEST/ FBC-BCA 107.1

 11/01/2022ELECTRIC FINAL**Joe NievesDISAPPROVED10/31/2022 7:34:34 AM ST 11/1/2022 12:23:08 PM Tech Required For Generator Electric Final On Site. FBC 107.1

 11/17/2022ELECTRIC FINAL**Joe NievesDISAPPROVED11/15/2022 6:59:00 AM INSPT CAME IN 11/14 AT 545PM Request For Inspection City of Parkland Request for Inspection Form Permit Number 21070099 First Name Bryan Last Name Bianco Company Bryco Electric LLc. Phone Number 5612897384 Email Address brycoelectricllc@gmail.com Type of Inspection(s) Requested Final Request Date 11/3/2022 Instructions/Example If you desire an inspection on the 28th, your request must be submitted by 4:00PM on the 27th. Additional Information Contractors can schedule inspections online by going to https://www.cityofparkland.org/epermit. If you are a contractor and do not have access to eTRAKiT please contact the Building Department to get directions for scheduling inspections online. Contractors can cancel inspections online up to 6:00am via the online portal. Same day inspection cancellations you must contact the Building Department via telephone between 7:30 and 8:00 AM at 954.753.5447. 11/17/2022 1:32:26 PM Technician Required For Generator Start-Up And Test/FBC-BCA 107.1

 12/14/2022ELECTRIC FINAL**Rinor KrasniqiDISAPPROVED12/12/2022 12:36:22 PM ST

 01/24/2023ELECTRIC FINAL**Rinor KrasniqiDISAPPROVED1/20/2023 12:56:35 PM ST 1/24/2023 1:33:25 PM 107.1 FCBA tech req for final

 03/20/2023ELECTRIC FINAL**Rinor KrasniqiDISAPPROVED - FEE3/9/2023 1:58:16 PM ST 3/20/2023 11:49:30 AM Technician Required For Generator Start-Up And Test/FBC-BCA 107.1

 04/03/2023ELECTRIC FINAL**Pedro VieiraDISAPPROVED3/31/2023 8:37:19 AM CJ 4/3/2023 3:06:27 PM No plans on site

 05/01/2023ELECTRIC FINAL**Pedro VieiraDISAPPROVED5/1/2023 2:59:25 PM No access 11:10am

 05/03/2023ELECTRIC FINAL**Pedro VieiraDISAPPROVED5/2/2023 10:36:16 AM MT 5/3/2023 10:34:38 AM No access 9:15am

 05/05/2023ELECTRIC FINAL**Rinor KrasniqiDISAPPROVED5/5/2023 10:32:41 AM 110.3 Reducing washer not rain tight 11p.14 Ground improperly terminated 110.3 Sealing locknut improperly installed 107.3.1 Plan not on site

 07/14/2023ELECTRIC FINAL**Joe NievesDISAPPROVED - FEE7/14/2023 1:22:19 PM Tech Required On Site For Generator Startup And Test. FBC-BCA 107.1

 08/30/2023ELECTRIC FINAL**Rinor KrasniqiDISAPPROVED - FEE8/28/2023 7:46:08 AM FM 8/30/2023 4:09:48 PM 107.1 tech required for gen final

 09/25/2023ELECTRIC FINAL**Joe NievesAPPROVED