03/14/2023 | NOC | Debbie Grosse | APPROVED | | |
|
06/08/2023 | LANDSCAPING | Patti Hoot | APPROVED | | 6/7/2023 1:40:27 PM
MT
|
|
06/08/2023 | UNDERGROUND | Joe Nieves | APPROVED | | 6/7/2023 1:40:50 PM
MT
6/8/2023 12:33:16 PM
Underground Inspection Not Required/ Generator Feeder Installed On The Exterior of Building.
|
|
06/08/2023 | ELECTRIC ROUGH | Joe Nieves | APPROVED | | 6/7/2023 1:40:04 PM
MT
|
|
06/09/2023 | MECHANICAL FINAL | Dave Chin-Sang | DISAPPROVED | | 6/8/2023 2:03:45 PM
ST
6/9/2023 9:53:55 AM
No permit paperwork on site.
Generator exhaust less than 10' to Soffit vent
|
|
06/09/2023 | FINAL GAS-PLUMBING | Dave Chin-Sang | DISAPPROVED | EXISTING TANK AND STUB OUT 2008-0060 | 6/8/2023 2:03:32 PM
ST
6/9/2023 9:53:56 AM
Permit paperwork not on site.
Regulator vent less than 5' to generator NFPA 58
6.10.1.6
|
|
06/09/2023 | FINAL GAS-FIRE | Fire Inspector | DISAPPROVED | EXISTING TANK AND STUB OUT 2008-0060 | 6/8/2023 2:03:12 PM
ST
6/9/2023 11:06:34 AM
Permit/Plans not on site.
NFPA 58 - Regulator vent less than 5'' to generator
|
|
06/30/2023 | MECHANICAL FINAL | Dave Chin-Sang | DISAPPROVED | | 6/29/2023 8:52:44 AM
ST
6/30/2023 9:49:20 AM
Eave vent less than 10' to generator exhaust
|
|
06/30/2023 | FINAL GAS-PLUMBING | Dave Chin-Sang | APPROVED | | 6/29/2023 8:52:23 AM
ST
|
|
06/30/2023 | FINAL GAS-FIRE | Lici Merritt | APPROVED | | 6/29/2023 8:55:42 AM
ST
7/6/2023 1:50:42 PM
Inspection completed by Inspector Botting.
|
|
08/03/2023 | MECHANICAL FINAL | Dave Chin-Sang | APPROVED | | 8/2/2023 3:00:43 PM
MT
|
|
08/08/2023 | ELECTRIC FINAL** | Pedro Vieira | DISAPPROVED | | 8/7/2023 8:30:30 AM
ST
8/8/2023 10:55:56 AM
No access
No technician on site to start generator to do final generator electrical inspection
10:05am
|
|
08/15/2023 | ELECTRIC FINAL** | Joe Nieves | APPROVED | | 8/14/2023 10:32:44 AM
ST
8/15/2023 1:17:58 PM
Approved Permit [Water Damaged] Unable To Sign/ Final Electric [Approved] Homeowner Will Seek Duplicate Permit.
|
|