Permit No. ELEC2212-0024 Permit Type   GENERATOR Site Address   6204 NW 74 TER
PARKLAND, FL 33067
Applied   12/02/2022 Applicant  
Approved   02/24/2023 Owner   FERNANDEZ,HECTOR
Issued   03/14/2023 Contractor   RESIDENTIAL & COMMERCIAL REPAIR SERVICE
Parent Permit No.   Description   GENERATOR W/ TANK ON EXISTING SLAB
  Notes  
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

 03/14/2023NOCDebbie GrosseAPPROVED

 06/08/2023LANDSCAPINGPatti HootAPPROVED6/7/2023 1:40:27 PM MT

 06/08/2023UNDERGROUNDJoe NievesAPPROVED6/7/2023 1:40:50 PM MT 6/8/2023 12:33:16 PM Underground Inspection Not Required/ Generator Feeder Installed On The Exterior of Building.

 06/08/2023ELECTRIC ROUGHJoe NievesAPPROVED6/7/2023 1:40:04 PM MT

 06/09/2023MECHANICAL FINALDave Chin-SangDISAPPROVED6/8/2023 2:03:45 PM ST 6/9/2023 9:53:55 AM No permit paperwork on site. Generator exhaust less than 10' to Soffit vent

 06/09/2023FINAL GAS-PLUMBINGDave Chin-SangDISAPPROVEDEXISTING TANK AND STUB OUT 2008-00606/8/2023 2:03:32 PM ST 6/9/2023 9:53:56 AM Permit paperwork not on site. Regulator vent less than 5' to generator NFPA 58 6.10.1.6

 06/09/2023FINAL GAS-FIREFire InspectorDISAPPROVEDEXISTING TANK AND STUB OUT 2008-00606/8/2023 2:03:12 PM ST 6/9/2023 11:06:34 AM Permit/Plans not on site. NFPA 58 - Regulator vent less than 5'' to generator

 06/30/2023MECHANICAL FINALDave Chin-SangDISAPPROVED6/29/2023 8:52:44 AM ST 6/30/2023 9:49:20 AM Eave vent less than 10' to generator exhaust

 06/30/2023FINAL GAS-PLUMBINGDave Chin-SangAPPROVED6/29/2023 8:52:23 AM ST

 06/30/2023FINAL GAS-FIRELici MerrittAPPROVED6/29/2023 8:55:42 AM ST 7/6/2023 1:50:42 PM Inspection completed by Inspector Botting.

 08/03/2023MECHANICAL FINALDave Chin-SangAPPROVED8/2/2023 3:00:43 PM MT

 08/08/2023ELECTRIC FINAL**Pedro VieiraDISAPPROVED8/7/2023 8:30:30 AM ST 8/8/2023 10:55:56 AM No access No technician on site to start generator to do final generator electrical inspection 10:05am

 08/15/2023ELECTRIC FINAL**Joe NievesAPPROVED8/14/2023 10:32:44 AM ST 8/15/2023 1:17:58 PM Approved Permit [Water Damaged] Unable To Sign/ Final Electric [Approved] Homeowner Will Seek Duplicate Permit.