04/28/2024
10:04 PM
 
Permit No. SOLR2104-0144 Permit Type   SOLAR Site Address   6505 NW 74 DR
PARKLAND, FL 330673930
Applied   04/09/2021 Applicant  
Approved   03/10/2022 Owner   IMAM,TANVIR
Issued   06/22/2022 Contractor   SUN4 INC
Parent Permit No.   Description   PHOTOVOLTAIC SYSTEM
  Notes  
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

 12/14/2022NOCJuan SotoAPPROVED

 04/10/2023SOLAR PANEL ATTACHJoseph RobinsonDISAPPROVED4/6/2023 9:30:04 AM JS 4/10/2023 12:47:02 PM No permit package posted. No ladder.

 04/10/2023ELECTRIC ROUGHJoe NievesPARTIAL APPROVALREQUESTING FINAL4/6/2023 9:30:29 AM JS 4/10/2023 1:24:29 PM Approved Plan And Permit Required For Rough Inspection/ FBC-BCA 107.3.1

 04/11/2023ELECTRIC ROUGHPedro VieiraCANCELLED BY PERMITE4/10/2023 3:12:15 PM ST 4/11/2023 12:40:58 PM No access No plans on site Contractor not on site No access to roof

 04/11/2023SOLAR PANEL ATTACHJoseph RobinsonCANCELLED BY PERMITE4/10/2023 3:12:59 PM ST

 04/12/2023ELECTRIC ROUGHJoe NievesPARTIAL APPROVAL4/12/2023 12:35:33 PM Partial Electric Rough Approved/Pending Change Of Plan/Pending Installation Of Correct 40 Amp Fuses.

 04/12/2023SOLAR PANEL ATTACHWill JorgeDISAPPROVED4/12/2023 4:06:40 PM installation system not per plan, rails used, not per plan

 06/09/2023ELECTRIC ROUGHJoe NievesAPPROVEDNo Approved Plans6/8/2023 10:47:29 AM ST 6/9/2023 7:02:05 AM Inspector EL18 changed the inspection assignment from EL18 to EL12

 06/13/2023SOLAR PANEL ATTACHAlejandro CorralesDISAPPROVEDNo Approved Plans6/12/2023 12:19:18 PM vb 6/13/2023 3:02:23 PM 1) All rooftop penetrations (solar stack pedestals) must be sealed with a cementitious or impermeable material. Open cell spray foam was used around penetrations but this will not repel water. Seal around broken tiles and solar stack pedestals Panel quantity, location and installation is ok.

 06/22/2023PE CERTIFICATIONWyatt T. HaygoodAPPROVED

 06/22/2023SOLAR PANEL ATTACHWill JorgeAPPROVED6/21/2023 11:00:02 AM ST

 06/23/2023ELECTRIC FINAL**Rinor KrasniqiDISAPPROVEDNo Approved Plans6/23/2023 10:39:37 AM Bonding screw may only be used to bond the can to the grounding conductor, and not to bond the grounding conductor, and the grounded conductor Wire bites improperly installed, live parts exposed 110.3

 06/27/2023ELECTRIC FINAL**Rinor KrasniqiDISAPPROVED6/26/2023 11:05:51 AM ST 6/27/2023 4:04:23 PM Incomplete, wires under panel #3 from the right touching tile

 06/30/2023ELECTRIC FINAL**Joe NievesAPPROVED6/29/2023 9:37:57 AM ST